Find 12kV Indoor HV Load Switch, Vacuum Load Switch, HV Load Break Switch on Industry Directory, Reliable Manufacturer/Supplier/Factory from China.

Inquiry Basket (0)
Home > Products > 12kV Indoor HV Load Switch > High Quality, Best Choice Indoor Hv Load Break Switch-Fn7-12D/630-20

High Quality, Best Choice Indoor Hv Load Break Switch-Fn7-12D/630-20

Basic Info

Model No.:  FN7-12D/630-20

Product Description

Model NO.: FN7-12D/630-20 Application: 3 Phase AC Power Stystem Certification: ISO9001,SGS, Ce Environment: Indoor High Voltage Origin: Jiangyin Yunfeng, China Type: Gas-Production High Voltage Arc-Extinguishing Principle: Arc Quenching Principle Test Equipment: IEC Standard Trademark: YF Product Overview
YFN7(FN7)-12 series indoor AC HV load switch is a gas-production HV load switch and fuse combination unit with arc quenching principle.It is applied in three-phase AC 50Hz power system with rated voltage 12kV for breaking the load current and making the short-circuit current.The fuse combination unit can break the short-circuit current and has the function of single-phase fuse three-phase tripping and breaking.It is the ideal selection for protecting the line, equipment and transformer. Its performance meets the requirements of national standards GB 3804-2004 High-voltage alternating-current switches for rated voltage above 3.6kV and less than 40.5kV and GB 16926-2009
High-voltage alternating current switch-fuse combinations.

Model Specification
Indoor AC HV load switch
High Quality, Best Choice Indoor Hv Load Break Switch-Fn7-12D/630-20
Note: The sensor with live display can be used for the Switch Insulator

Characteristics:
          ---small size
          ---light weight
          ---simple & reasonable structure
          ---small operating force
          ---reliable performance & convenient maintenance

Service Conditions
         1.Altitude≤1000m;
          2.Ambient temperature-25ºC-+ 40ºC;
          3.The daily average of relative humidity shall not be larger than 95% and the monthly average shall not be               larger than 90%:
          4.The ambient air shall not be subject to the obvious pollution such as corrosive or combustible gas and                   steam;
          5.The site without fire hazards and explosion hazards;
          6.The site that the seismic intensity does not exceed degree 8; the gradient shall not exceed 5°

Main Technical Parameters
Serial No. Item Unit YFN7-12 HV Load Switch
1 Rated voltage kV 12
2 Rated frequency HZ 50
3 Rated current A 630
4 Rated short-circuit breaking current of fuse kA ---
5 Rated breaking transfer current A ---
6 Main loop resistance μΩ ≤80
7 Rated active load breaking current A 630
8 Rated short-time withstand current(thermal stability current)/duration kA/s 20/4
9 Rated short-time withstand current(thermal stability current)/duration of Earthing Switch  kA/s 16/2
10 Rated peak withstand current(dynamic current) kA 50
11 1 min power-frequency withstand voltage(effective value)to earth,phase-to-phase/isolating fracture kV/kV 42/48
12 Full-wave lightning impluse withstand voltage(peak) to earth,phase-to-phase/isolating fracture kV/kV 75/85
13 Mechanical life Time 2000
14 Rated opening operation voltage V ---
15 Time of switch opening triggered by breaking of fuse ms ---


High Quality, Best Choice Indoor Hv Load Break Switch-Fn7-12D/630-20

High Quality, Best Choice Indoor Hv Load Break Switch-Fn7-12D/630-20High Quality, Best Choice Indoor Hv Load Break Switch-Fn7-12D/630-20High Quality, Best Choice Indoor Hv Load Break Switch-Fn7-12D/630-20







 

Contact us if you need more details on Load Break Switch. We are ready to answer your questions on packaging, logistics, certification or any Other aspects about Isolator Switch、Disconnector. If these products fail to match your need, please contact us and we would like to provide relevant information.