Basic Info

Model No.:  FZN35-40.5D

Product Description



Model NO.: FZN35-40.5D


Structure: Scientific and National Structure


Pole: 3


Number of Switch: Multi Control Switch


Environment: Indoor High Voltage


Operation Mode: Manual or Electric Operation


Trademark: YF




Function: Industry


Usage: Break Load/Overload/Short-Circuit Current


Rated Continuous Current: 630


Certification: SGS, ISO9001, CE


Test Equipment: IEC Standard


Application: The Network with a.C50Hz,Rated Voltage 40.5kv


Origin: Jiangyin Yunfeng, China


1.Product Overview

YFZN35-40.5D/T 1250-20 indoor A.C high-voltage Vacuum Load Switch and YFZRN35-40.5D/T63-31.5 indoor A.C high-voltage switch-fuse fuse combiner (hereinafter referred to as "YFZN35-40.5 series vacuum load switch") are self-researched and manufactured by the company according to standards of GB3804-2004 and GB16926-1997, designed especially for 35kv box substation. It can also be use in power system as an independent electric unit. This product is featured by small size, easy installation, simple operation with scientific and national structure, flexible and reliable and obvious isolated fracture. The load switch can be free from maintenance, combined electrical apparatus can be matched with series striker pin fuse and it is safer and convenient to replace fuse.



2. Application

YFZN35-40.5 series vacuum load switch is used in the network with A.C50Hz,rated voltage 40.5kv, for breaking load current, overload current and short circuit current. Operation mode is divided into manual and electric functions, especially applied to the places required for oil and maintenance free and frequent operation.



Fzn35-40.5D-with Earthing Switch Load Switchgear for Indooor Use



3.Model Specification

Fzn35-40.5D-with Earthing Switch Load Switchgear for Indooor Use





Fzn35-40.5D-with Earthing Switch Load Switchgear for Indooor Use

Note: Insulator of switch can be matched with live display sensor.



4. Applicable environment

1. Altitude is not more than 1000m

2. Ambient air temperature comes to -25ºC~+40ºC

3. Relative humidity: daily average value is not more than 95%; steam pressure: daily average value is not more than 2.2kpa and monthly average value is not more than 1.8kpa

4. Ambient air shall not clearly polluted by air dust, corrosive or flammable gas, vapor, or salt spray, etc

5. In the secondary system, inductive electromagnetic amplitude value shall not be more than 1.6kv



Fzn35-40.5D-with Earthing Switch Load Switchgear for Indooor Use

5. Main technical parameters

a. Electric performance parameters

Serial No. Items Unit Load Switch Combined Electric Appliance Grounding Switch
1 Rated voltage k 40.5 40.5 40.5
2 Rated current A 1250 63 -
3 Rated frequency Hz 50 50 50
4 Rated short-circuit breaking current KA - 31.5
5 Rated line charging breaking current A 2.1 2.1
6 Rated grounding fault breaking current A 63 63
7 Rated short-circuit switching on and off current KA 50 - -
8 Rated peak value withstand current KA 50 - 50
9 Rated short-time withstand current/duration KA/s 20/4 - 20/2
10 Rated breaking transfer (cross connecting) current A - 1700 -
11 Rated active load breaking current A 1250 - -
12 Rated closed loop breaking current A 1250 - -
13 Rated cable charging current A 21 21 -
14 Secondary circuit operating rated voltage V AC/DC220,110
15 1 min power frequency withstand voltage(effective value),related to earth, phase, vacuum fracture/isolating fracture KV 95/118
16 Full wave lightning impulse withstand voltage(peak value), related to earth, phase, vacuum fracture/isolating fracture KV 185/215
17 Main circuit resistor μΩ 120 (excluding fuse of combined electric appliance)
18 Mechanical service life Time 5000 2000 2000
19 Max./ min. energy storage and tripping operating voltage V AC242/187
20 Max./ min. tripping operating voltage V AC264/143
21 Switch grade phase M2/E2 M1 M1/E0






b.Mechanical performance parameters

Serial No. Items Unit Vacuum Arc Extinguishing Chamber Isolation Knife Grounding Knife
1 Opening distance of contact mm 17±1 ≥350 -
2 Over-stroke of contact mm 4±1 - -
3 Average tripping speed m/s 1.6±0.2 - -
4 Average closing speed m/s 0.8±0.2 - -
5 Tri-polar switching on and off different stages ms 2 3mm -
6 Contact tripping bouncing time ms 2 -
7 Inter-polar central distance mm 410±2 410±2 410±2
8 Tripping and closing operation knife N 200b






c. Electro-dynamic parameters of spring operation mechanism

Permanent-magnet single-phase D.C energy-storage motor

Table 3

Model Rated Voltage Rated Output Power Normal Work Voltage Range
ZYJ220-53 AC/DC220V ≤70W 85%~110%Rated voltage




Tripping electromagnet(independent power supply)

Table 4

Rated Work Voltage(V) AC220 AC110 DC220
Rated Work Current(A) 2.67 2.93 2
Rated Electric Power (W) <587 <312 440
At 20 degrees centigrade coil resistance value (Ω) 30 ±3 18±1.7 58±10
Normal Work Voltage Range It switches off reliably 65% ~120% rated work voltage and can not switch off less than 30% rated work voltage.








Fzn35-40.5D-with Earthing Switch Load Switchgear for Indooor Use





6. Structure and Principle

a. Basic structure

1. YFZN35-40.5 series vacuum load switch is mainly composed of frame, vacuum arc extinguishing chamber, Isolation Switch, fuse,grounding knife, tipping transmission unit and spring operation mechanism. Isolation knife, vacuum arc extinguishing chamber are fixed on frame with isolator, fuse is installed on the back of isolation knife. The main shaft of grounding knife is installed on the bottom of frame directly. Spring operation mechanism is installed on the side plate of frame. Operation mode is side operation. Operation mechanism drives main shaft of switch, main shaft rotates and drives vacuum arc extinguishing chamber or isolation knife to act with crutch through Insulation operation bar, realizing the switch knife opening and closing operation. Grounding knife are connected to isolation knife with transmission link. When operating, two units interact with reliable mechanical interlock.



b. Work principle

1. Operation of vacuum arc extinguishing chamber

The spring operation mechanism allocated in YFZN35-40.5series vacuum load switch can adopt electric operation (see Fig.3 for control circuit wiring diagram). When switching on, the motor gear box drives switching-on spring, finishing energy storage and release directly. When switching-off operation, send switching-off impulse signal to electromagnet directly, switching-off electromagnet acts, impacting switching-off principal quantum, switching-off spring releases and vacuum arc extinguishing chamber finish switching off; it also can operate spring operation mechanism on operation panel manually: turn 180 degrees in the switching-on direction in load switch handle hole with operation handle, the manual switching on operation for vacuum arc extinguishing chamber is finished. Press switching-off button on operating panel, switch off vacuum arc extinguishing chamber. Whether in switching-off position or in switching-on position, the related "off" or "on" indication will display in the state indication hole of vacuum arc extinguishing room.



2. Switching on and off operation for isolation knife and grounding knife

The reliable mechanical interlocks are fixed between vacuum arc extinguishing chamber of YFZN35-40.5series vacuum load switch and isolation knife as well as grounding knife, only when vacuum arc extinguishing chamber is in switching-off state, can it operate isolation knife and grounding knife. Isolation knife interacts with grounding knife. When isolation knife switches off, insert operation handle into operation hole of isolation knife and turn 90 degrees in the switching-off direction, the isolation knife switches off. Go on operating handle and turns 60 degrees in the switching-off direction, grounding knife storages energy and finish switching on. At this time, state indication hole of isolation knife displays "off"; when operating isolation knife to switch on, it shall guarantee vacuum arc extinguishing chamber is in the switch-off state, turn operating handle at 60 degrees in the switching-off direction in the operation hole of isolation knife, and grounding knife switches off. Go on turning the handle at 90 degrees in the switching-off direction and isolation knife switches off. At this time, it displays "on" in the isolation knife state indication hole.



3. Fuse impacts tripping and switch off

Fuse tripping unit of FZN35-40.5 series vacuum load switch is three-stage interaction, the matched fuse shall be striker pin fuse. Tripping unit is flexible and reliable, when tripping impact power comes to medium sized 1-3J (Joule), it can switch off vacuum arc extinguishing chamber. The combined electrical apparatus in the switching-on position, when short-circuit current or overload current passes the main circuit, the fusant of any one of the three-phase fuse burns out, impacter acts, impacting the mechanical locking device of combined electrical appliance and realizing three phases of the vacuum arc extinguishing chamber to switch off reliably and swiftly under the action of tripping spring.



Fzn35-40.5D-with Earthing Switch Load Switchgear for Indooor Use



Contact us if you need more details on Earthing Switch. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Disconnector、Load Break Switch. If these products fail to match your need, please contact us and we would like to provide relevant information.