Home > Products > Circuit Breaker > 630A 24kv Vs1 Handcart Type Vcb with Assembly Pole

630A 24kv Vs1 Handcart Type Vcb with Assembly Pole

Basic Info

Model No.:  VS1

Product Description

Model NO.: VS1 Operation: Manual & Electric Vacuum Circuit Breaker Arc-extinguishing Medium: Vacuum Structure: Vcb Vacuum Circuit Breaker Type: Circuit Breaker Certification: ISO9001-2000, Ohsas 180001 Rated Current: 630A Vacuum Circuit Breaker Rated Frequency: 50Hz Vacuum Circuit Breaker Specification: CE, SGS, TUV HS Code: 8535210000 Breaking Capacity: Middle& High Voltage Vacuum Circuit Breaker Speed: Normal Type Circuit Breaker Installation: Fixed & Withdrawable Vacuum Circuit Breaker Poles Number: 3 Function: Overcurrent Protection Rated Voltage: 24kv Vacuum Circuit Breaker Mechnical Life: 1000times Vacuum Circuit Breaker Trademark: Mingde Vacuum Circuit Breaker Origin: Zhejiang Ningbo Vacuum Circuit Breaker 630A 24kv Vs1 Handcart Type VCB with Assembly Pole

Overview

 1. VS1A series of vacuum circuit breakers are the Second Generation indoor switch equipment, with the rated voltage 7.2kv, 12kv, 17.5kv and 24kv.   2. VS1A series of vacuum circuit breakers adopt the integrated design of simple structure and convenient operation.   3. It is equipped with a perfect mechanical and electrical interlock to enhance its anti-incorrect operation performance.   4. Standards: IEC62271-100, IEC56, GB1984-2003, GB/T11022, DL/T403-2000, etc.     Main Specifications and Technical Parameters 

 
Item unit Data
Rated voltage kV 24
1 min power frequency withstand voltage kV 65
 
Lightning impulse withstand voltage kV 125
Rated frequency Hz 50
Rated current A 630
Rated short-time withstand current kA 20,25,31.5
Rated peak withstand current kA 50,63,80
Rated short-circuit breaking current kA 20,25,31.5
Rated short-circuit closing current kA 50,63,80
Rated short-circuit duration S 4
Contact over-travel mm 3.5±0.5
Clearance between open contacts mm 13±1
Average opening speed m/s 1.3±0.3
Average closing speed m/s 0.8±0.2
Opening time ms 35-60
Closing time ms 20-45
Rated operation sequence   O-0.3s-CO-180s-CO(<40kA)/
O-180s-CO-180s-CO(≥40kA)
Mechanical life cycles 10000

External Dimension
630A 24kv Vs1 Handcart Type Vcb with Assembly Pole
 VS1A-24kv-pole center distance 210mm 
No. Rated Voltage(kV) Rated current(A) Short-circuit breaking current(kA) h1(mm) h2(mm) h(mm) B(mm)
1 24 630 20-31.5 325 310 768 747
2 24 1250 20-31.5 325 310 768 747
3 24 1250 31.5-40 345 310 768 747
4 24 1600 20-40 345 310 768 747




630A 24kv Vs1 Handcart Type Vcb with Assembly Pole
 VS1A-24kv-pole center distance 275mm 
No. Rated Voltage(kV) Rated current(A) Short-circuit breaking current(kA) h1(mm) h2(mm) h(mm) B(mm)
1 24 630 20-31.5 325 310 768 747
2 24 1250 20-31.5 325 310 768 747
3 24 1600 20-31.5 345 310 768 747
4 24 1600-2500 20-31.5 345 310 813 737
  Normal Operating Environment Condition

a) Normal operating environment condition
Highest temperature:                  +40ºC
Lowest temperature:                   -15ºC
b) Environment humidity
Daily mean relative humidity:        ≤95%
Monthly mean relative humidity:     ≤90%
Daily mean saturated vapor pressure:   ≤2.2×10-3 MPa
Monthly mean saturated vapor pressure:  ≤1.8×10-3 MPa
c) Altitude: below 1000m area;
d) Earthquake intensity: no more than 8 degree;
e) The product shall be away from weep, fire and explosion, chemical corrosion and strenuous vibration 
place.

Special Operating Condition

Please consult with manufacturer on manufacturing technology when operating environment is the climatic environment with high altitude, high humidity and great temperature change or Other special environment condition.
  Packaging, Transportation and Storage Precautions

(1) Circuit breaker should be in the state of opening and energy storage spring in a state without energy storage when packing. It should be in the state of opening and energy storage spring in a state without energy storage when packing. And it should be fixed on the bottom of the wooden case, should have waterproof measures and complete package labels.
(2) Circuit breakers can't invert and avoid strong vibration, rain, surface damage, and components lost when transportation.
(3) When loading the circuit breaker, we suggest the following tools: crane, forklift and driving. When lifting the circuit breaker, we should not hook on the body or pole of the circuit breaker, but on the lifting hole which has the lifting mark.
(4) When circuit breaker has a long-term storage, it should be in a state of opening and energy storage spring in a state without energy storage and placed in dry ventilated indoor preventing from moisture, vibration control and harmful gas erosion, and regularly checked whether environment meets the requirements.
(5)When first use products after long-term storage, it need to have a power frequency withstand voltage Insulation testing.
 
630A 24kv Vs1 Handcart Type Vcb with Assembly Pole
     

Contact us if you need more details on Circuit Breaker. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Breaker、Vacuum Circuit Breaker. If these products fail to match your need, please contact us and we would like to provide relevant information.

Product Categories : Circuit Breaker