24kv-2000A Vs1 Indoor Embedded Structure Vacuum Circuit Breakers
Basic Info
Model No.: VS1
Product Description
Model NO.: VS1 Operation: Manual & Electric Circuit Breaker Arc-extinguishing Medium: Vacuum Structure: Vcb Circuit Breaker Type: Circuit Breaker Certification: ISO9001-2000, Ohsas 180001 Rated Current: 2000A Circuit Breaker Rated Frequency: 50Hz Circuit Breaker Specification: CE, ISO9001, OHSAS18001 HS Code: 8535210000 Breaking Capacity: Middle& High Voltage Circuit Breaker Speed: Normal Type Circuit Breaker Installation: Fixed & Withdrawable Circuit Breaker Poles Number: 3 Function: Overcurrent Protection Rated Voltage: 24kv Circuit Breaker Mechnical Life: 1000times Circuit Breaker Trademark: Mingde Circuit Breaker Origin: Zhejiang Ningbo Circuit Breaker 24kV-2000A Vs1 Indoor Embedded Structure Vacuum Circuit Breakers
Overview
1. VS1A series of vacuum circuit breakers are the Second Generation indoor switch equipment, with the rated voltage 7.2kv, 12kv, 17.5kv and 24kv.
2. VS1A series of vacuum circuit breakers adopt the integrated design of simple structure and convenient operation.
3. It is equipped with a perfect mechanical and electrical interlock to enhance its anti-incorrect operation performance.
4. Standards: IEC62271-100, IEC56, GB1984-2003, GB/T11022, DL/T403-2000, etc.
Main Specifications and Technical Parameters
Normal Operating Environment Condition
a) Normal operating environment condition
Highest temperature: +40ºC
Lowest temperature: -15ºC
b) Environment humidity
Daily mean relative humidity: ≤95%
Monthly mean relative humidity: ≤90%
Daily mean saturated vapor pressure: ≤2.2×10-3 MPa
Monthly mean saturated vapor pressure: ≤1.8×10-3 MPa
c) Altitude: below 1000m area;
d) Earthquake intensity: no more than 8 degree;
e) The product shall be away from weep, fire and explosion, chemical corrosion and strenuous vibration
place.
Special Operating Condition
Please consult with manufacturer on manufacturing technology when operating environment is the climatic environment with high altitude, high humidity and great temperature change or Other special environment condition.
Packing & Delivery
Production Show
Certification
Contact us if you need more details on Circuit Breaker. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Breaker、Vacuum Circuit Breaker. If these products fail to match your need, please contact us and we would like to provide relevant information.
Overview
1. VS1A series of vacuum circuit breakers are the Second Generation indoor switch equipment, with the rated voltage 7.2kv, 12kv, 17.5kv and 24kv.
2. VS1A series of vacuum circuit breakers adopt the integrated design of simple structure and convenient operation.
3. It is equipped with a perfect mechanical and electrical interlock to enhance its anti-incorrect operation performance.
4. Standards: IEC62271-100, IEC56, GB1984-2003, GB/T11022, DL/T403-2000, etc.
Main Specifications and Technical Parameters
Item | unit | Data |
Rated voltage | kV | 24 |
1 min power frequency withstand voltage | kV | 65 |
Lightning impulse withstand voltage | kV | 125 |
Rated frequency | Hz | 50 |
Rated current | A | 2000 |
Rated short-time withstand current | kA | 20,25,31.5 |
Rated peak withstand current | kA | 50,63,80 |
Rated short-circuit breaking current | kA | 20,25,31.5 |
Rated short-circuit closing current | kA | 50,63,80 |
Rated short-circuit duration | S | 4 |
Contact over-travel | mm | 3.5±0.5 |
Clearance between open contacts | mm | 13±1 |
Average opening speed | m/s | 1.3±0.3 |
Average closing speed | m/s | 0.8±0.2 |
Opening time | ms | 35-60 |
Closing time | ms | 20-45 |
Rated operation sequence | O-0.3s-CO-180s-CO(<40kA)/ O-180s-CO-180s-CO(≥40kA) | |
Mechanical life | cycles | 10000 |
Normal Operating Environment Condition
a) Normal operating environment condition
Highest temperature: +40ºC
Lowest temperature: -15ºC
b) Environment humidity
Daily mean relative humidity: ≤95%
Monthly mean relative humidity: ≤90%
Daily mean saturated vapor pressure: ≤2.2×10-3 MPa
Monthly mean saturated vapor pressure: ≤1.8×10-3 MPa
c) Altitude: below 1000m area;
d) Earthquake intensity: no more than 8 degree;
e) The product shall be away from weep, fire and explosion, chemical corrosion and strenuous vibration
place.
Special Operating Condition
Please consult with manufacturer on manufacturing technology when operating environment is the climatic environment with high altitude, high humidity and great temperature change or Other special environment condition.
Packing & Delivery
Packing details | Standard export package (wooden case) suitable for long-distance ocean transportation and though handling |
Delivery details | Depends on ordered quantity |
Production Show
Certification
Contact us if you need more details on Circuit Breaker. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Breaker、Vacuum Circuit Breaker. If these products fail to match your need, please contact us and we would like to provide relevant information.
Product Categories : Circuit Breaker
Premium Related Products
Other Products
Hot Products
Fuse Combination Unit Load Break Switch with Grounding Knife-Yfn5-12r (T) D/125-31.5Reasonble Price for Zinc-Oxide Lightning ArresterCkg Series High-Voltage Vacuum ContactorFn5-12r (T) D-Hv Load Switch with Reasonable Price.Hxgn-24 Indoor Ring Net Cabinet with High Quality, Reasonble PriceBest Selling, Reasonable Price&Good Service of Yfzn35-40.5 Series Vacuum Load Switch with FuseYFZRN-24 AC Hv Vacuum Load Switch with Safe and Easy Fuse12kv Series Factory Manufacture High-Voltage Isolating Switch--Yfg38-12D12kv Vacuum Arc Extinction High-Voltage Circuit Breaker Indoor Use -Vs1Fn5-12r (T) D Indoor AC Hv Load Switch-Fuse Combination UnitContact Box Md/150Mdgear 550 Solid Insulation Metal-Clad SwitchgearKyn61 Clad-Metal Drawable AC Metal Closed Switchgear550 Modularized Omni-Sealed Solid Insulation Metal-Clad Switchgear12kv Vs1 Indoor High-Voltage Vacuum Circuit Breaker with Embedded Pole12kv 630A Vmd Hv Electric Vacuum Breaker