Basic Info

Model No.:  VMV

Product Description

Model NO.: VMV Operation: Manual and Electrical Type Circuit Breaker Arc-extinguishing Medium: Vacuum Structure: Vcb Circuit Breaker Type: Circuit Breaker Certification: ISO9001-2000, CE Rated Voltage: 12kv Circuit Breaker Lightning Impluse Withstand Voltage: 75kv Circuit Breaker Specification: SGS, Tuv HS Code: 8535210000 Breaking Capacity: High and Medium Voltage Circuit Breaker Speed: Normal Type Circuit Breaker Installation: Fixed and Handcart Type Circuit Breaker Poles Number: 3 Function: Overcurrent Protection Rated Current: 1600A Circuit Breaker Rated Withstand Curent: 50/63/80ka Circuit Breaker Trademark: Mingde Circuit Breaker Origin: Cixi, Ningbo, Zhejiang Circuit Breaker 12kv -1600A Vmv High  Quality VCB in Switchgear

Overview

1. A brand new series of products, wider use in different fields and environment
2. Mechanical life up to 60,000 times
3. Expandable to smart circuit breaker
 
Operation Mechanism

VMV Modularized Operation Mechanism (with smart unit)
Modularized design of the operation mechanism is the highlights of VMV circuit breaker. With opening module and closing module in one part, the independent operation mechanism makes the standardized production and maintenance much easier.
 
Gear Driving System

We improved VMV circuit breakers' driving system, using the gear driving system instead of the traditional chain wheel driving system. The circuit breaker operation will run more smoothly with a longer mechanical life.

Opening Oil Buffer

The application of high-performance oil buffer can greatly reduce moving contact's over-swing and rebound during the circuit breakers' opening process. In this way, it avoids the reduction of mechanical life when vacuum interrupter is over-fatigue, resulted from contact's over-swing.
 
External Dimensions


12kv -1600A Vmv High Quality Vcb in Switchgear
 VMV 12----pole center distance 150mm 
No. Rated Voltage(kV) Rated current(A) Short-circuit breaking current(kA) h1(mm) h2(mm) h(mm) A(mm) B(mm)
1   12 630-1250 20-31.5 260 205 622 438 609
2   12 630-1250 20-31.5 280 275 637 432 598
 
12kv -1600A Vmv High Quality Vcb in Switchgear VMV 12----pole center distance 210mm 
No. Rated Voltage(kV) Rated current(A) Short-circuit
 breaking current(kA)
h1(mm) h2(mm) h(mm) A(mm) B(mm)
1  12 630-1250 20-31.5 260 205 622 438 609
2  12 630-1600 20-31.5 280 275 637 432 598
3  12 1250-1600 40 295 310 697 432 598
4  12 2000 31.5-40 295 310 697 432 598
 
 
12kv -1600A Vmv High Quality Vcb in SwitchgearVMV 12- pole center distance 275mm 
No. Rated Voltage(kV) Rated current(A) Short-circuit breaking 
current(kA)
h1(mm) h2(mm) H(mm) A(mm) B(mm)
1 12 630-1250 20-31.5 280 275 637 432 598
2 12 1250-1600 40 295 310 697 432 598
3 12 1600-2500 25-40 295 310 697 432 586
4 12 3150-4000 31.5-40 295 310 697 432 586
5 12 3150-4000 31.5-40 295 310 733 432 586

 Main Specifications and Parameters
 

Item

unit

Data

Rated voltage

kV

12

1 min power frequency withstand voltage

kV

42

 

Lightning impulse withstand voltage

kV

75

Rated frequency

Hz

50

Rated current

A

1250

Rated short-time withstand current

kA

 20,25,31.5

Rated peak withstand current

kA

50,63,80

Rated short-circuit breaking current

kA

20,25,31.5

Rated short-circuit closing current

kA

50,63,80

Rated short-circuit duration

S

4

Contact over-travel 

mm

3.5±0.5

Clearance between open contacts

mm

9±1/11±1

Average opening speed

m/s

1.1±0.2

Average closing speed

m/s

0.6±0.2

Opening time 

ms

35-60

Closing time

ms

20-45

Rated operation sequence

 

O-0.3s-CO-180s-CO(<40kA)/

O-180s-CO-180s-CO(40kA)

Mechanical life

cycles

10000,30000,60000

 
Packaging, transportation and storage precautions

(1) Circuit breaker should be in the state of opening and energy storage spring in a state without energy storage when packing. It should be in the state of opening and energy storage spring in a state without energy storage when packing. And it should be fixed on the bottom of the wooden case, should have waterproof measures and complete package labels.
(2) Circuit breakers can't invert and avoid strong vibration, rain, surface damage, and components lost when transportation.
(3) When loading the circuit breaker, we suggest the following tools: crane, forklift and driving. When lifting the circuit breaker, we should not hook on the body or pole of the circuit breaker, but on the lifting hole which has the lifting mark.
(4) When circuit breaker has a long-term storage, it should be in a state of opening and energy storage spring in a state without energy storage and placed in dry ventilated indoor preventing from moisture, vibration control and harmful gas erosion, and regularly checked whether environment meets the requirements.
(5)When first use products after long-term storage, it need to have a power frequency withstand voltage Insulation testing.

Contact us if you need more details on Circuit Breaker. We are ready to answer your questions on packaging, logistics, certification or any Other aspects about Vacuum Circuit Breaker、Breaker. If these products fail to match your need, please contact us and we would like to provide relevant information.