12kv Indoor 3150A Embedded Structure Vmv Vacuum Circuit Breakers
Basic Info
Model No.: VMV
Product Description
Overview
1. A brand new series of products, wider use in different fields and
environment
2. Mechanical life up to 60,000 times
3. Expandable to smart circuit breaker
Operation Mechanism
VMV Modularized Operation Mechanism (with smart unit)
Modularized design of the operation mechanism is the highlights of VMV circuit breaker. With opening module and closing module in one part, the independent operation mechanism makes the standardized production and maintenance much easier.
Gear Driving System
We improved VMV circuit breakers' driving system, using the gear driving system instead of the traditional chain wheel driving system. The circuit breaker operation will run more smoothly with a longer mechanical life.
Opening Oil Buffer
The application of high-performance oil buffer can greatly reduce moving contact's over-swing and rebound during the circuit breakers' opening process. In this way, it avoids the reduction of mechanical life when vacuum interrupter is over-fatigue, resulted from contact's over-swing.
External Dimensions
VMV 12----pole center distance 150mm
No. | Rated Voltage(kV) | Rated current(A) | Short-circuit breaking current(kA) | h1(mm) | h2(mm) | h(mm) | A(mm) | B(mm) |
1 | 12 | 630-1250 | 20-31.5 | 260 | 205 | 622 | 438 | 609 |
2 | 12 | 630-1250 | 20-31.5 | 280 | 275 | 637 | 432 | 598 |
VMV 12----pole center distance 210mm
No. | Rated Voltage(kV) | Rated current(A) | Short-circuit breaking current(kA) | h1(mm) | h2(mm) | h(mm) | A(mm) | B(mm) |
1 | 12 | 630-1250 | 20-31.5 | 260 | 205 | 622 | 438 | 609 |
2 | 12 | 630-1600 | 20-31.5 | 280 | 275 | 637 | 432 | 598 |
3 | 12 | 1250-1600 | 40 | 295 | 310 | 697 | 432 | 598 |
4 | 12 | 2000 | 31.5-40 | 295 | 310 | 697 | 432 | 598 |
VMV 12----pole center distance 275mm
No. | Rated Voltage(kV) | Rated current(A) | Short-circuit breaking current(kA) | h1(mm) | h2(mm) | H(mm) | A(mm) | B(mm) |
1 | 12 | 630-1250 | 20-31.5 | 280 | 275 | 637 | 432 | 598 |
2 | 12 | 1250-1600 | 40 | 295 | 310 | 697 | 432 | 598 |
3 | 12 | 1600-2500 | 25-40 | 295 | 310 | 697 | 432 | 586 |
4 | 12 | 3150-4000 | 31.5-40 | 295 | 310 | 697 | 432 | 586 |
5 | 12 | 3150-4000 | 31.5-40 | 295 | 310 | 733 | 432 | 586 |
Main Specification and Parameters
Item | unit | Data |
Rated voltage | kV | 12 |
1 min power frequency withstand voltage | kV | 42
|
Lightning impulse withstand voltage | kV | 75 |
Rated frequency | Hz | 50 |
Rated current | A | 3150 |
Rated short-time withstand current | kA | 20,25,31.5,40 |
Rated peak withstand current | kA | 50,63,80,100 |
Rated short-circuit breaking current | kA | 20,25,31.5,40 |
Rated short-circuit closing current | kA | 50,63,80,100 |
Rated short-circuit duration | S | 4 |
Contact over-travel | mm | 3.5±0.5 |
Clearance between open contacts | mm | 9±1/11±1 |
Average opening speed | m/s | 1.1±0.2 |
Average closing speed | m/s | 0.6±0.2 |
Opening time | ms | 35-60 |
Closing time | ms | 20-45 |
Rated operation sequence |
| O-0.3s-CO-180s-CO(<40kA)/ O-180s-CO-180s-CO(≥40kA) |
Mechanical life | cycles | 10000,30000,60000 |
a) Normal operating environment condition
Highest temperature: +40ºC
Lowest temperature: -15ºC
b) Environment humidity
Daily mean relative humidity: ≤95%
Monthly mean relative humidity: ≤90%
Daily mean saturated vapor pressure: ≤2.2×10-3 MPa
Monthly mean saturated vapor pressure: ≤1.8×10-3 MPa
c) Altitude: below 1000m area;
d) Earthquake intensity: no more than 8 degree;
e) The product shall be away from weep, fire and explosion, chemical corrosion and
strenuous vibration place.
Special Operating Condition
Please consult with manufacturer on manufacturing technology when operating environment is the climatic environment with high altitude, high humidity and great temperature change or Other special environment condition.
Packaging, Transportation and Storage Precautions
(1) Circuit breaker should be in the state of opening and energy storage spring in a state without energy storage when packing. It should be in the state of opening and energy storage spring in a state without energy storage when packing. And it should be fixed on the bottom of the wooden case, should have waterproof measures and complete package labels.
(2) Circuit breakers can't invert and avoid strong vibration, rain, surface damage, and components lost when transportation.
(3) When loading the circuit breaker, we suggest the following tools: crane, forklift and driving. When lifting the circuit breaker, we should not hook on the body or pole of the circuit breaker, but on the lifting hole which has the lifting mark.
(4) When circuit breaker has a long-term storage, it should be in a state of opening and energy storage spring in a state without energy storage and placed in dry ventilated indoor preventing from moisture, vibration control and harmful gas erosion, and regularly checked whether environment meets the requirements.
(5)When first use products after long-term storage, it need to have a power frequency withstand voltage Insulation testing.
Contact us if you need more details on Vacuum Circuit Breaker. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Circuit Breaker、Electrical Breaker. If these products fail to match your need, please contact us and we would like to provide relevant information.