Model No.:  FN12-12RD

Product Description

Model NO.: FN12-12RD Usage: Control Switch Number of Switch: Multi Control Switch Arc-Extinguishing Principle: Air-Compresing Type: Indoor High Voltage Trademark: YF Function: Industry, Circuit-Breaker Failure Protection Pole: 3 Certification: SGS, ISO9001, CE Test Equipment: IEC Standard Operation Model: Manual or Electric Operation Origin: Jiangyin Yunfeng, China Product Overview
YFN12(FN12)-12 series indoor AC HV load switch works under the air-compressing arc extinction principle. Because of its unique structural design, it can make full use of the air-compression extinguishing arc generated in the trippingprocess of switch. Its performance meeets the requirements of national standards GB 3804-2004 High-voltage alternating-current switches for rated voltage above 3.6kV and less than 40.5kV and GB 16926-2009 High-voltage alternating current switch-fuse combinations.It is applied in the HV AC 12kV network with the frequency of 50HZ for opening, closing the load current, overload current and making the short-circuit current. Together with the HV current-limiting fuse and trip device, it combines YFN12-12R series indoor AC HV load switch-fuse combination unit, which can reliably disconnect the 
rated short-circuit current.

Model Specification
Fn12-12rd--Indoor Use High Voltage Load Break Switch with Fuse
Fn12-12rd--Indoor Use High Voltage Load Break Switch with Fuse
Characteristics:
          ---small size
          ---light weight
          ---simple & reasonable structure
          ---small operating force
          ---reliable performance & convenient maintenance

Service Conditions
          1.Altitude≤1000m;
          2.Ambient temperature-25ºC-+ 40ºC;
          3.The daily average of relative humidity shall not be larger than 95% and the monthly average shall not be               larger than 90%:
          4.The ambient air shall not be subject to the obvious pollution such as corrosive or combustible gas and                   steam;
          5.The site without fire hazards and explosion hazards;
          6.The site that the seismic intensity does not exceed degree 8; the gradient shall not exceed 5°

Main Technical Parameters
Serial No. Item Unit YFN12-12R HV Load Switch-Fuse Combination Unit
1 Rated voltage KV 12
2 Rated frequency Hz 50
3 Rated current A Max.rated current of fuse equipped:125A
4 Rated short-circuit breaking current of fuse kA 31.5; 40; 50
5 Rated breaking-transfer(handover) current A 1700
6 Rated active load breaking current A 630
7 5% rated active load breaking current A 31.5
8 Rated closed loop breaking current A 630
9 Rated cable charging breaking current A 10
10 Rated short-time withstand current       ---Load switch kA/s 20/3
(thermal stability current)/duration        ---Earthing Switch kA/s 16/2
11 Rated short-circuit making current kA 50
12 Rated peak withstand current(dynamic stability current) kA 50
13 1min power-frequency withstand voltage(effective value) to earth, phase-to-phase/isloating fracture kV/kV 42/48
14 Full-wave lightning impulse withstand voltage(peak)to earth,phase-to-phase/isolating fracture kV/kV 75/85
15 Main loop resistance μΩ ≤120
16 Mechnical life Time 2000
17 Three-phase opening and closing asynchronization ms ≤5
18 Inter-pole center distance mm 210±5
19 Distance between live parts and of phase to earth mm ≥140
20 Opening closing operation torque of load switch N·m ≤80
21 Opening closing operation torque of earth switch N·m ≤35
22 Rated closing operation voltage V ≌220/110
23 Rated opening operation voltage V ≌220/110
24 Time of switch opening triggered by breaking of fuse  ms 35±5
25 Impact output energy at breaking of fuse J(Joule) 1





 

Contact us if you need more details on Load Break Switch. We are ready to answer your questions on packaging, logistics, certification or any Other aspects about Fuse、Switchgear. If these products fail to match your need, please contact us and we would like to provide relevant information.

Product Categories : HV Load Break Switch With Fuse