Model NO.: YFGZN35VD-40.5 Operation: Electric Type Arc-extinguishing Medium: Vacuum Poles Number: 3 Function: Overcurrent Protection Trademark: YF Breaking Capacity: High Voltage Circuit Breakers Speed: High-Speed Circuit Breaker Installation: Fixed Type: Circuit Breaker Certification: ISO9001-2000, IEC & GB Origin: Jiangyin Yunfeng, China Product Overview
YFGZ35-40.5D/T1250-25 indoor AC HV Vacuum Circuit Breaker with disconnector is applied in the three-phase AC 50 Hz network with the rated voltage40.5kV. It is a vacuum circuit breaker with obvious isolating fracture in conformity to GB1984-2003. It can be also applied to the power system as an independent electrical unit for breaking load current, overload current and short-circuit current.It is also applied to the situation with different nature load and frequent operation. It has the function of protection and control for electrical installations industry and mining enterprises, power plant and power transformation substation.

Model Specification
Yfgzn35vd-40.5D Vacuum Circuit Breaker with CT and Disconnector

Characteristics
         a.simple but reasonable structure
         b.small operation force
         c.reliable performance 
         d.convenient maintenance

Service Conditions
          1.Altitude1000m;
          2.Ambient temperature-25ºC-+ 50ºC;
          3.The daily average of relative humidity shall not be larger than 95% and the monthly average shall not be               larger than 90%:
          4.The ambient air shall not be subject to the obvious pollution such as corrosive or combustible gas and                   steam;
          5.The site without fire hazards and explosion hazards;
          6.No frequent severe vibration

Main Technical Parameters
Serial No. Item Unit YFGZ35-40.5 Vacuum Circuit Breaker
1 Rated voltage  kV 40.5
2 Rated frequency Hz 50
3 Rated current A 630/1250
4 Rated short-circuit breaking current kA 25/31.5
5 Rated short-circuit making current kA 63/80
6 Rated short-time withstand current(thermal stability current)/duration kA/s 25/4   31.5/4
7 Rated peak withstand current(dynamic stability current)/duration kA- 63  80
8 Rated short-circuit breaking current breaking time time 30
9 Rated 1 min power-frequency withstand voltage(effective value) kV 95
10 Rated lightning impluse withstand voltage(peak) kV 185
11 Rated operation sequence   0-0.3s-co-180s-co
12 Clearance between open contacts mm 18±1
13 Overtravel(spring compression length of contact) mm 3.5±0.5
14 Contact closing bounce time ms ≤3
15 Three-phase opening and closing asynchronization ms ≤2
16 Average opening speed m/s 1.6±0.2
17 Average closing speed  m/s 0.65±0.2
18 Mechanical life time 10000
19 Rated current breaking times(electrical endurance) time 2000
20 Main loop resistance μΩ ≤120
21 Gross thickness of allowable wear of dynamic and static contact mm 3

 

Contact us if you need more details on Vacuum Circuit Breaker. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Disconnector、Protection. If these products fail to match your need, please contact us and we would like to provide relevant information.