Find Indoor HV Vacuum Circuit Breaker, Vacuum Circuit Breaker, Load Break Switch on Industry Directory, Reliable Manufacturer/Supplier/Factory from China.

Inquiry Basket (0)
Home > Products > Indoor HV Vacuum Circuit Breaker > Yfgzn35vd-40.5-Vacuum Circuit Breaker with Disconnector

Yfgzn35vd-40.5-Vacuum Circuit Breaker with Disconnector

Basic Info

Model No.:  YFGZN35VD-40.5

Product Description



Model NO.: YFGZN35VD-40.5


Operation: Electric Type


Arc-extinguishing Medium: Vacuum


Poles Number: 3


Function: Overcurrent Protection


Trademark: YF




Breaking Capacity: High Voltage Circuit Breakers


Speed: High-Speed Circuit Breaker


Installation: Fixed


Type: Circuit Breaker


Certification: ISO9001-2000, IEC & GB


Origin: Jiangyin Yunfeng, China


Product Overview

YFGZ35-40.5D/T1250-25 indoor AC HV Vacuum Circuit Breaker with disconnector is applied in the three-phase AC 50 Hz network with the rated voltage40.5kV. It is a vacuum circuit breaker with obvious isolating fracture in conformity to GB1984-2003. It can be also applied to the power system as an independent electrical unit for breaking load current, overload current and short-circuit current.It is also applied to the situation with different nature load and frequent operation. It has the function of protection and control for electrical installations industry and mining enterprises, power plant and power transformation substation.



Model Specification

Yfgzn35vd-40.5-Vacuum Circuit Breaker with Disconnector



Yfgzn35vd-40.5-Vacuum Circuit Breaker with Disconnector



Characteristics

a.simple but reasonable structure

b.small operation force

c.reliable performance

d.convenient maintenance



Yfgzn35vd-40.5-Vacuum Circuit Breaker with Disconnector



Service Conditions

1.Altitude1000m;

2.Ambient temperature-25ºC-+ 50ºC;

3.The daily average of relative humidity shall not be larger than 95% and the monthly average shall not be larger than 90%:

4.The ambient air shall not be subject to the obvious pollution such as corrosive or combustible gas and steam;

5.The site without fire hazards and explosion hazards;

6.No frequent severe vibration



Yfgzn35vd-40.5-Vacuum Circuit Breaker with Disconnector



Main Technical Parameters

Serial No. Item Unit YFGZ35-40.5 Vacuum Circuit Breaker
1 Rated voltage kV 40.5
2 Rated frequency Hz 50
3 Rated current A 630/1250
4 Rated short-circuit breaking current kA 25/31.5
5 Rated short-circuit making current kA 63/80
6 Rated short-time withstand current(thermal stability current)/duration kA/s 25/4 31.5/4
7 Rated peak withstand current(dynamic stability current)/duration kA- 63 80
8 Rated short-circuit breaking current breaking time time 30
9 Rated 1 min power-frequency withstand voltage(effective value) kV 95
10 Rated lightning impluse withstand voltage(peak) kV 185
11 Rated operation sequence 0-0.3s-co-180s-co
12 Clearance between open contacts mm 18±1
13 Overtravel(spring compression length of contact) mm 3.5±0.5
14 Contact closing bounce time ms ≤3
15 Three-phase opening and closing asynchronization ms ≤2
16 Average opening speed m/s 1.6±0.2
17 Average closing speed m/s 0.65±0.2
18 Mechanical life time 10000
19 Rated current breaking times(electrical endurance) time 2000
20 Main loop resistance μΩ ≤120
21 Gross thickness of allowable wear of dynamic and static contact mm 3






Yfgzn35vd-40.5-Vacuum Circuit Breaker with Disconnector

Contact us if you need more details on Circuit Breaker. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Vacuum Load Switch、Isolate Switch. If these products fail to match your need, please contact us and we would like to provide relevant information.

Product Categories : Indoor HV Vacuum Circuit Breaker

Email to this supplier
  • *Subject:
  • To:

  • *Messages:
    Your message must be between 20-8000 characters