Find 24kV Indoor HV Load Switch, Load Break Switch, Vacuum Switchgear on Industry Directory, Reliable Manufacturer/Supplier/Factory from China.

Inquiry Basket (0)
Home > Products > 24kV Indoor HV Load Switch > Jn15-24 Series Indoor AC Hv Grounding Switch

Jn15-24 Series Indoor AC Hv Grounding Switch

Basic Info

Model No.:  JN15-24

Product Description

Model NO.: JN15-24 Model No.: Jn15-24 Certification: ISO Origin: Jiangyin Yunfeng, China Environment: Indoor High Voltage Usage: Electrical Appliance Trademark: YF JN15-24
Product Overview
JN15-24 series Indoor AC HV Earthing Switch(hereinafter referred to as eathing switch) is applied to indoor grounding device with rated voltage 24kV, three-pole alternating current 50Hz. Its performance meets the requirements of the national standards GB 1985-2004 High-voltage Alternating current Disconnector and Grounding switch. It can be used in armoured and movable type AC metal enclosed switchgear. According to requirements of Safety Work Order, when the electric equipment power outage, the earthing switch should be closed to make grounding short circuit artificially to guarentee the maintainers can get safe and reliable ground potential protection. At the same time, with live display device,it can prevent turning off the earthing switch. Once the error occurred, it can avoid Other equipment from being damaged with making capacity. 

Model Specification
Jn15-24 Series Indoor AC Hv Grounding Switch

Jn15-24 Series Indoor AC Hv Grounding SwitchJn15-24 Series Indoor AC Hv Grounding Switch

Characteristics
   1. simple and compact structure
   2.light weight
   3.small operation force
   4.convenient installation
   5.can be equipped with all different kinds of high voltage live display devices
   6.can be applied in different type of high voltage switch cambinet
   7. the function of grounding protection when high-voltage electric equipment is under examining and repairing    

Main Technical Parameters
Seial No Item Unit  Data
1 Rated voltage kV 24
2 Rated frequency Hz 50
3 Rated short-time withstand current(thermal stability current) kA 25/31.5
4 Rated short-time withstand current duration S 4
5 Rated peak withstand current(dynamic stability current) kA 63/80
6 Rated short-circuit making current kA 63/80
7 Rated 1 min power-frequency withstand voltage  kV 65
8 Rated lightning implus withstand voltage kV 125
9 Fracture distance after switch opening mm ≥190
10 Mechanical life Time 2000

 Service Conditions
       1.Altitude≤1000m;
       2.Ambient temperature-25ºC-+ 40ºC; stored temperature-30ºC;
       3.The daily average of relative humidity shall not be larger than 95% and the monthly average shall not be               larger than 90%;
       4.The site that the seismic intensity does not exceed degree 8; the gradient shall not exceed 5°.

 

Contact us if you need more details on Earthing Switch. We are ready to answer your questions on packaging, logistics, certification or any other aspects about High Voltage、Switchgear. If these products fail to match your need, please contact us and we would like to provide relevant information.

Product Categories : 24kV Indoor HV Load Switch